Permit Number: T04CM04219
Parcel: 11004345J

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04219
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2004 JIM EGAN FIRE REVIEW Approved
10/07/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/07/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
10/07/2004 GERRY KOZIOL WWM REVIEW Approved
10/07/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
10/07/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/07/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM04219 DENIED 10/06/04

Please make the following corrections/clarifications to panel load calculations:
1. Add 25% of HP-3 as continuous load.
2. Add 25% of Ckts 5,7,9,and 11 as continuous load.
3. It appears that total for Phase A is 8059, not 7963.
4. Correct panel total.
10/07/2004 ROBERT SHERRY WATER REVIEW Approved
10/07/2004 JIM TATE ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/07/2004 TAMI ACHONG OUT TO CUSTOMER Completed