Review Details: OTHER
Permit Number - T04CM04206
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/04/2004 | JIM EGAN | FIRE | REVIEW | Approved | Occupant load for restaurant shall not exceed 50. |
| 10/05/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM04206 DENIED 10/05/04 1. Minimum font size is 10 point. 2. Provide lighting fixture schedule. 3. Provide Legend/Key to Symbols. 4. Provide a disconnect for the Walk-In Cooler Compressor. 5. Provide overcurrent protection for the Walk-In Cooler compressor per NEC 430 or NEC 440, whichever is applicable. See NEC 422.11 (G). 6. Specify circuit breaker size for A-23,25. 7. Ckt A-31,33 with 5000 VA, would draw 20.8A. A 20A circuit does not appear adequate. 8. Ckt B-6,8 with 5200 VA, would draw 21.7A. A 20A circuit does not appear adequate. |
| 10/22/2004 | Raul Palma | BUILDING-COMMERCIAL | REVIEW | Needs Review |