Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T04CM04204
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/14/2004 | Jim Egan | FIRE | REVIEW | Denied | 1. Fire hydrant required. 2. Submit correct code review checklist. Justify B-Occupancy classification throughout. |
| 10/19/2004 | Robert Suba | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.Please clear up sheet e-1. Min. font size is 12. 2.Clarify comment regarding afc "shall be greater than or equal to" ? I think you ment "less than or equal" ? |
| 10/21/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Increase the minimum size of the fonts to 10 points. 2. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2003, for business occupancy. 3. Provide water supply and waste & vent schematics. Reference Section 103.2.3, UPC 1994. 4. Revise the site drawing to show the location and size of the water meter and the size of the reduced pressure backflow preventer assembly. Reference Section 103.2.3, UPC 1994. 5. Revise the site drawing to show the slope of the building drain and the required cleanouts. Reference Section 103.2.3, UPC 1994. 6. Provide the rim elevation of the next upstream and the next downstream sanitary manholes and the first floor elevation. Determine the need for a backwater valve per Section 710.1, UPC 1994. 7. Revise the plumbing fixture schedule using the fixture unit values shown in Tables 6-3 and 7-3, UPC 1994. Reference Section 703.1, UPC 1994. 8. Provide material standards for all plumbing fixtures being provided by others. Reference Section 103.2.3, UPC 1994. 9. Specify the type, capacity and efficiency of the water heater and provide a detail showing how the water heater is to be piped. Reference Section 103.2.3, UPC 1994. 10. All storage-type water heaters require a listed expansion tank. Please show expansion tanks on plans. Reference Section 608.3, UPC 1994 with AZ State amendments. 11. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping along with ½" insulation on the first eight feet of supply and discharge piping. Reference Sections 804.4 and 804.5, IECC 2000. 12. Include all fixtures and the water requirements of the HVAC equipment when calculating the total demand and determining pipe sizes. Reference Section 610.1, UPC 1994. 13. Provide calculations showing water supply piping is sized in accordance with Section 610.4, UPC 1994. 14. Limit the water velocity to less than 8 fps for the PVC and Copper piping. Reference Section A 6.1, UPC 1994; IAPMO IS 3-93, Section 610.0; and IAPMO IS 8-92, Section 610.1. 15. Clarify which piping is to be above grade and which is to be below grade. Show piping to all fixtures and to the HVAC equipment. Reference Section 103.2.3, UPC 1994. 16. Show the natural gas meter and piping on the drawing. Provide the natural gas pipe sizing calculations. Include gas pressures and developed pipe lengths on plans. Reference Section 1217.0, UPC 1994 with AZ State amendments. |
| 10/21/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Increase the minimum size of the fonts to 10 points. 2. Provide energy code compliance calculations. Reference Section 101.2, International Energy Conservation Code 2000. 3. Provide sufficient heat for the shop area to maintain a minimum temperature of 68°F on a design heating day (32°F). Reference Section 309.1, IMC 2000. 4. Provide calculations demonstrating adequate ventilation in the office areas. Reference Section 401, IMC 2000. 5. Ventilation for restrooms in public spaces requires a minimum of 75 CFM of mechanical exhaust per water closet or urinal. Reference Sections 403.2.1 (3) and 403.3, IMC 2000. 6. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference Section 803.2.8, IECC 2000. 7. Show the size, routing, and termination of the condensate drain. Reference Section 307.2, IMC 2000 and Section 807.2, UPC 1994. 8. Show the size, routing, and termination of the drains from the evaporative coolers. Reference Section 106.3.1, IMC 2000. |
| 10/21/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/25/2004 | David Rivera | ZONING | REVIEW | Denied | Site plan approval required. |
| 10/26/2004 | Paul Machado | ENGINEERING | REVIEW | Denied | Approved site plan required. |
| 11/15/2004 | Gerry Koziol | WWM | REVIEW | Denied | 1: Trade service building 2: need to show location/method of connection to public sewer. 3: needs par/non-par wastewater evaluation-5th floor. |
| 11/16/2004 | SREEVES1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | plan check stopped due to NSF |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/18/2005 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 02/18/2005 | SUE REEVES | REJECT SHELF | Completed |