Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T04CM04187
Parcel: 129133240

Address:
949 E 35TH ST

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T04CM04187
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2004 JIM EGAN FIRE REVIEW Approved
10/04/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the site drawing to show the sizes and routes of the building water supplies along with the location of both the water meter and the reduced pressure backflow preventer assembly. Reference Section 103.2.3, UPC 1994.
2. Include all existing fixtures served by a single meter when calculating the total demand and determining pipe sizes. Reference Section 610.1, UPC 1994.
3. Provide water pressure and water pipe sizing calculations. Reference Appendix A, UPC 1994.
4. Revise the drawing so that the size of the RPBP located after the meter complies to Section 610.2, UPC 1994.
5. Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 710.1, UPC 1994.
6. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (drain lines serving sinks require cleanouts regardless of length). Reference Section 707.4, UPC 1994.
10/04/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Terminate the condensate drain for AC-1 in accordance with Section 307.2.1, IMC as amended by the City of Tucson.
2. Clarify the total amount of supply air provided by AC-1 (Shown as 1400 CFM on M1.1 and as both 1400 CFM and 1800 CFM on M2.1).
3. Correct the ventilation calculations for AC-1: (50x348)/1000 = 17.4, not 8. Note also that the calculation for Section 403.3.2 is also incorrect.
10/04/2004 ROBERT SHERRY WATER REVIEW Approved
10/20/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. On Sheet E1 Electrical Site Plan, it appears that one of the Key symbols "2" should read "5".
2. Specifications make several references to pre-2002 NEC. Examples: "250-94" and "250-95" on pages 16-34 and 16-35. Please convert all such references to their 2002 counterpart.
3. Please submit a cut sheet for new Fixture D.
4. Please provide IECC calculations for lighting power budget. Such calcs were submitted for Buildings B and C. Note: it does not appear that Building B LPB calcs should be required on Building B.
5. Please add a note to the plans requiring the contractor to provide TEP available fault current, and to install equipment rated for such AFC.
6. Per NEC 230.2, a second service may not be installed on this building. According to the Building Plans Examiner, the wall between D and A is not a fire wall. If this were a fire wall, then A and D could be considered as separate buildings per Article 100.
10/21/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 10/20/04
ACTIVITY NUMBER: T04CM04185, T04CM04186, T04CM04187, T04CM04188
PROJECT NAME: OFFICE BLDG, DUPLEX, ART STUDIO, & ART STUDIO
PROJECT ADDRESS: 951 E. 35th st.
ARCHITECT / ENGINEER: POSTER FROST ASSOC.
PROJECT REVIEWER: CHRISTY FOREMAN



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1. SEE DEMO PERMIT REQUIREMENTS FOR THE TWO BUILDINGS TO BE REMOVED. A COPY OF THE APPROVED AIR QUALITY ACTIVITY EQUIPMENT OPERATING PERMIT.
2. RESTROOM FACILITIES BUILDING D - SEE CODE SECTION 2902.4 A VARIANCE FROM THIS CODE SECTION WOULD REQUIRE A APPEAL TO THE BUILDING OFFICIAL.
3. 4/18 STRUCTURAL CALCULATIONS - WHAT BUILDING? IF BUILDING 'B' WEIGHT OF UNIT = 320# DOES NOT MATCH STRUCTURAL CALCULATIONS.
4. RAMADA TYP. JOIST 6/18 STRUCTURAL CALCULATIONS USE <3X3X3/16 SHT. S1.1 CALLS OUT <3X3X1/4.
5. SHT. S1.1 - NOTE 6 SPECIFIES FOR MECH. UNITS ON ROOF- SEE ROOF FRAMING KEYNOTES NOTE 6 = 2X8 LEDGER.
6. JUSTIFY/ CLARIFY EXTERIOR WALL OPENINGS IN 1 HR. RATED WEST WALL.
7. JUSTIFY EXTERIOR WALL OPENINGS IN 1 HR. RATED WEST WALL.
8. HOLD DOWN LOCATIONS ON BLDG. C & D NEED TO BE SHOWN ON FOUNDATION PLAN.
9. CLARIFY / JUSTIFY 1 HR SEPERATION BETWEEN DUPLEXES AT BLDG. 'B'
10. STRUCTUAL CALCULATIONS - CANTILEVERED RETAINING WALL WHERE IS THE DETAIL ON THE DRAWINGS AND WHERE IS IT LOCATED ON SITE.
11. BLDG. 'A' - RESTROOM A102 FIG. 404.2.4.1 MANEUVERING CLEARANCE AT SWINGING DOORS ANSI A117.1 - EXITING THE RESTROOM.
12. CLARIFY OCCUPANT LOAD FOR BLDG. A, D & C.
13. BLDG. 'D' 101 - CLARIFY SINKS COMPLY WITH ANSI 117.1 SECTION 606 - LAVATORIES AND SINKS.
14. BLDG. 'C' TURNING RADIUS SHOULD NOT ENCROACH ON DOOR SWING. SEE ANSI STANDARDS 117.1
15. SAFETY GLAZING - BLDG. 'A' WINDOW NEXT TO DOOR. PLEASE CLARIFY.
16. TABLE 2902.1 ALL USE GROUP B - 1 DRINKING FOUNTAIN REQUIRED FOR EACH BLDG. PLEASE CLARIFY.
11/01/2004 Gerry Koziol WWM REVIEW Denied need 8th floor waste water credit evaluation
11/01/2004 DOUG WILLIAMS ENGINEERING REVIEW Approved
11/03/2004 DAN CASTRO ZONING REVIEW Denied Zoning Review may not approve the building plans prior to Structural Review approval.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/08/2004 TAMI ACHONG OUT TO CUSTOMER Completed
11/08/2004 ANGIE SHOFFSTALL REJECT SHELF Completed