The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T04CM04187
Parcel: 129133240

Address:
949 E 35TH ST

Review Status: Completed

Review Details: REVISION - WALK THRU

Permit Number - T04CM04187
Review Name: REVISION - WALK THRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/12/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM04187 12/7/05

1. Use of the "c" value for the fault calculation implies the equivalent of #2, which has ampacity of 115A. This does not appear correct, because Panel D tallys over 100a without the addition of Panel A's load.