| 12/12/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM04187 12/7/05 1. Use of the "c" value for the fault calculation implies the equivalent of #2, which has ampacity of 115A. This does not appear correct, because Panel D tallys over 100a without the addition of Panel A's load. |