12/07/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM04184 DENIED 12/07/04
1. It is unclear where on site this building is to be located. Plot on site plan, and include TEP equipment as well.
2. Provide TEP available fault current for 200A 3-phase 208 V is 13,900 A. Provide fault calculations to demonstrate that the equipment can is properly rated.
3. Registrant shall sign and date seal.