| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/13/2005 | DSTARK1 | BUILDING-COMMERCIAL | REVIEW | Stop | |
| 12/07/2004 | ANY | ZONING | REVIEW | Stopped | |
| 12/07/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM04184 DENIED 12/07/04 1. It is unclear where on site this building is to be located. Plot on site plan, and include TEP equipment as well. 2. Provide TEP available fault current for 200A 3-phase 208 V is 13,900 A. Provide fault calculations to demonstrate that the equipment can is properly rated. 3. Registrant shall sign and date seal. |