Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04184
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/16/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | CLARIFY RESTROOM FACILITITES. |
| 09/16/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 09/16/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM04184 DENIED 9/16/04 1. It is unclear where on site this building is to be located. Plot on site plan, and include TEP equipment as well. 2. Provide fixture cut sheets for exterior fixtures. Such fixtures shall be suitable for their exterior application, and shall comply with the Outdoor Lighting Ordinance, http://www.ci.tucson.az.us/dsd/Codes___Ordinances/Outdoor_Lighting_Code.pdf. 3. Add 25% to panel loads for largest motor and exterior lighting. 4. Provide TEP available fault current and fault calculations. 5. Change reference to 1999 NEC in Note 1 to reference 2002 NEC. 6. Note 4 refers to ceiling fans. None indicated in legend, electrical plan, or panel schedule. Please clarify. |
| 09/16/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/16/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 12/07/2004 | DROBEY1 | FIRE | REVIEW | Needs Review | |
| 12/07/2004 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 12/07/2004 | DROBEY1 | ZONING | REVIEW | Needs Review | |
| 12/07/2004 | DROBEY1 | ENGINEERING | REVIEW | Needs Review |