Permit Number: T04CM04178
Parcel: 105102410

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM04178
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM04178 DENIED 9/21/04


1. Barber receptacles appear to be low on electrical load count on panel schedule. Consider a couple of blow dryers for example.
2. Ckt A-29, with 4 receptacles, should be counted at a minimum of 180 VA per receptacle for a total of 0.7, not 0.4 VA.
09/23/2004 GERRY KOZIOL WWM REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/05/2004 TAMI ACHONG OUT TO CUSTOMER Completed