Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/23/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM04178 DENIED 9/21/04 1. Barber receptacles appear to be low on electrical load count on panel schedule. Consider a couple of blow dryers for example. 2. Ckt A-29, with 4 receptacles, should be counted at a minimum of 180 VA per receptacle for a total of 0.7, not 0.4 VA. |
09/23/2004 | GERRY KOZIOL | WWM | REVIEW | Completed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/05/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |