Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2004 JIM EGAN FIRE REVIEW Approved
09/16/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/16/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
09/16/2004 ROBERT SHERRY WATER REVIEW Approved
09/16/2004 PATRICIA GEHLEN ZONING REVIEW Approved
09/16/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/16/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM04178 DENIED 9/16/04

1. Panel voltage indicated is 120/1. This is not reasonable given the circuit distribution and loads. Please clarify.
2. It appears that Ckt A-32,44 on Electrical Plan should read "A-32,34.
3. Barber receptacles appear to be low on electrical load count on panel schedule. Consider a couple of blow dryers for example.
4. Note 3 please change the reference to 1999 NEC to read: "2002".
09/16/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
09/21/2004 EGRANT1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/21/2004 BETH GRANT OUT TO CUSTOMER Completed