Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04178
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/16/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 09/16/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 09/16/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/16/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/16/2004 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 09/16/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/16/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM04178 DENIED 9/16/04 1. Panel voltage indicated is 120/1. This is not reasonable given the circuit distribution and loads. Please clarify. 2. It appears that Ckt A-32,44 on Electrical Plan should read "A-32,34. 3. Barber receptacles appear to be low on electrical load count on panel schedule. Consider a couple of blow dryers for example. 4. Note 3 please change the reference to 1999 NEC to read: "2002". |
| 09/16/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 09/21/2004 | EGRANT1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/21/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |