Permit Number: T04CM04174
Parcel: 14016011A

Review Status: Completed

Review Details: SITE

Permit Number - T04CM04174
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2004 Jim Egan FIRE REVIEW Approved
09/17/2004 ANDREW CONNOR NPPO REVIEW Denied Previously approved development plan indicates that protected trees (Prosopis velutina) are located within the landscape median if any trees are removed mitigation will apply per LUC TABLE 3.8.6-I
09/17/2004 Andrew Connor LANDSCAPE REVIEW Denied 1. Revise landscape plan to include the same quantities and species of shrubs and trees indicated in the landscape legend within the Development Plan Case #D01-008 per CCD Policy 4 (4.8)


2. Choose symbols that reflect the ultimate size of plants indicated by the spread of canopy, circumference of shrubs, or spread of ground cover per DS 2-07.2.2.A.1.c

3. Previously approved development plan indicates that protected trees (Prosopis velutina) are located within the landscape median if any trees are removed mitigation will apply per LUC TABLE 3.8.6-I
10/04/2004 Peter McLaughlin ZONING REVIEW Denied SITE PLAN TRANSMITTAL

TO: Philip Hawtin
Summit Project Delivery 8916 Cardiff Place
Stockton, CA 95210
(209) 481-9497

FROM: Peter McLaughlin
Senior Planner
Development Services Dept.

FOR: Patricia Gehlen
Principal Planner
Development Services Dept.

PROJECT:
T04CM04174
T-Mobile Kiosk
1790 E. Irvington Road
Site Plan Review (1st review)

TRANSMITTAL: October 5, 2004

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.


1. This project was reviewed as a less than 25% expansion.
DS 2-02

2. Between any building and PAAL, a minimum 5-foot pedestrian refuge area is required. The refuge areas must include a four-foot wide concrete sidewalk that is physically separate from the PAAL. There is no pedestrian refuge area shown along the west side of the proposed building. Please detail and dimension pedestrian sidewalk/refuge areas adjacent to the buildings. Also, a minimum 4-foot sidewalk is required between the south side of the building and the parking area.
DS 3-05.2.2.B.1
DS 2-08.4.1.C

3. A wheelstop curb must be placed in the northernmost parking space where vehicles may park and overhang the required pedestrian sidewalk (see comment 2). Dimension the wheelstops from the front of parking spaces per DS 3-05.2.3.C.2. Wheelstop curbing is to be located 2-½ feet from the front of parking spaces.
DS 3-05.2.3.C

4. Pedestrian circulation must be continuous and show direct connections between the buildings and adjacent rights-of way. Show pedestrian connection to other buildings and adjacent streets.
DS 2-02.2.1.A.12
DS 2-08.4.1.A & .D

5. For microfilming/archiving purposes, all lettering and dimensions must be a minimum of 12 (0.12") point in size. Please revise all text to meet this standard.
DS 2-05.2.1.C

6. Indicate in the site data that the required MS&R street perimeter yard building setback along Irvington Road is the greater of 21 feet or height of exterior structure wall measured from the back of future curb location.
LUC 3.2.6.5

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.
10/05/2004 PETER MCLAUGHLIN HANDICAP-SITE REVIEW Approved
10/08/2004 Doug Williams ENGINEERING REVIEW Denied October 11, 2004

Site Review - T Mobile (Campbell/Irvington)
Engineering Division Comments
Development Services Department

Reviewer:
Doug Williams, Sr. Engineering Associate

1. Label the structure's proposed finished floor elevation on sheets Z-2 and Z-3, relative to the elevations provided with the submittal package (ALTA Survey).

2. Provide a detail, fully labeled and dimensioned, for the proposed addition of a dumpster within the existing onsite dumpster enclosure. Depict solid waste vehicle maneuverability and accessibility to the enclosure, in accordance with Development Standard 6-01.0 (Dev. Std 2-02.2.1 A 32).

3. The existing enclosure depicted does not match the approved Development Plan (D01-008), and appears to be in conflict with a nearby loading zone. The Development Plan may need to be submitted for review and approval for this revision prior to, or in conjunction with a resubmittal. Please contact Patricia Gehlen, Zoning/CDRC Manager or her designee, for clarification of this matter.

If you have any questions, please feel free to contact me at 791-5550 ext. 1189, or via email at DWillia1@ci.tucson.az.us

Final Status

Task End Date Reviewer's Name Type of Review Description
10/20/2004 LISA LESNY OUT TO CUSTOMER Completed
10/20/2004 LISA LESNY REJECT SHELF Completed