Permit Number: T04CM04169
Parcel: 136261300

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04169
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
09/20/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The governing code is the 1994 UPC with State of Arizona Amendments.
2. Show how the water piping was sized.
09/20/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM04169 DENIED 9/20/04

1. Add electrical requirements to lighting fixture descriptions, such as voltage, wattage.
2. According to the panel schedule the sign circuit is entered as continuous load. This being the case, please change 1200 VA to 1500 VA.
3. Provide for grounding of the telephone system per NEC 800.40. Specify grounding conductor size and point of attachment.
4. It appears that Ckt C1-7 should have 360 VA, not 180.
5. Station receptacle circuits are counted at 180 VA per receptacle, which is questionable. Verify equipment wattages with client, and clarify circuit loading. Note that the 180 VA is a Code minimum in 220.3 (B) for general use receptacles. Work station receptacles in a salon are NOT for general use.
6. There is a branch circuit to B-28. No Panel B this project.
7. AC unit is described as 36 MCA on Sheet E1, and 22 MCA on panel schedule. Pls clarify.
09/20/2004 ROBERT SHERRY WATER REVIEW Approved
09/20/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide ventilation for the barber shop per Section 403.3, IMC 2000.
10/12/2004 DROBEY1 FIRE REVIEW Needs Review
10/12/2004 DROBEY1 WWM REVIEW Needs Review
10/12/2004 DROBEY1 ZONING REVIEW Needs Review
10/12/2004 DROBEY1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/12/2004 DELMA ROBEY OUT TO CUSTOMER Completed