Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04169
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/20/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/20/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The governing code is the 1994 UPC with State of Arizona Amendments. 2. Show how the water piping was sized. |
| 09/20/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM04169 DENIED 9/20/04 1. Add electrical requirements to lighting fixture descriptions, such as voltage, wattage. 2. According to the panel schedule the sign circuit is entered as continuous load. This being the case, please change 1200 VA to 1500 VA. 3. Provide for grounding of the telephone system per NEC 800.40. Specify grounding conductor size and point of attachment. 4. It appears that Ckt C1-7 should have 360 VA, not 180. 5. Station receptacle circuits are counted at 180 VA per receptacle, which is questionable. Verify equipment wattages with client, and clarify circuit loading. Note that the 180 VA is a Code minimum in 220.3 (B) for general use receptacles. Work station receptacles in a salon are NOT for general use. 6. There is a branch circuit to B-28. No Panel B this project. 7. AC unit is described as 36 MCA on Sheet E1, and 22 MCA on panel schedule. Pls clarify. |
| 09/20/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/20/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide ventilation for the barber shop per Section 403.3, IMC 2000. |
| 10/12/2004 | DROBEY1 | FIRE | REVIEW | Needs Review | |
| 10/12/2004 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 10/12/2004 | DROBEY1 | ZONING | REVIEW | Needs Review | |
| 10/12/2004 | DROBEY1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/12/2004 | DELMA ROBEY | OUT TO CUSTOMER | Completed |