Permit Number: T04CM04163
Parcel: 123061470

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM04163
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2005 NEAL SAUNDERS BUILDING-RESIDENTIAL REVIEW Denied SEE PREVIOUS COMMENTS. NONE WERE ADDRESSED.
ALSO, ADDRESS THESE COMMENTS FOR THE GARAGE AND PORCH ADDITION.

1. Show calculation of attic ventilation area in compliance with R806.2. Note location of all vents needed to comply.(GARAGE)
2. Over-framing - If solid sheathing is used on the lower trusses, provide minimum openings of 22" by 30" for access and ventilation into over-framed areas (>30 S.F.). If solid sheathing is not used on lower trusses, provide details for bracing of top chord of lower trusses.
3. Note feeder sizes to new sub-panel in garage.
4. Specify guest house rooms adjacent garage addition. Bedroom egress may be an issue?
5. Provide zoning approved site plan with garge addition and prch addition. Note all dimensions from property lines to all structures.
6. Remove constuction plans for carport if it is not to be built.
04/11/2005 DAN CASTRO ZONING REVIEW Denied COMMENTS: Previous comments from review dated 3/4/05 were not addressed. A garage is now being included in the permit application. Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. a) Please note the exterior building wall heights for all structures being permitted on site plan sheet 1 as follows:
Maximum height of new structures = ____
Height of exterior walls for new additions:
North: ____ feet high
South: ____ feet high
East: ____ feet high
West: ____ feet high

b) Building height shall be measured from design grade.

2. Dimension building wall heights on elevation drawings for all structures being permitted.

3. Dimension building setbacks from north property line and west property line to existing carport, proposed garage, and guest house. In addition, provide a copy of the last approved site plan to verify that both of these structures have been permitted. You may check the records section for a copy of the approved site plans or permits.

4. Dimension building setback from west property line to new addition.

5. Tucson Blvd. is designated a major street by the Major Streets and Routes (MS&R) Plan with a total right-of-way of 76 feet. Please label and dimension the "existing" and "future" right-of-way and existing and future curb location for Tucson. Face of "future" curb will be located nine (9) feet in front of the future right-of-way line. Building setback to proposed family room and carport may not be verified for compliance until this information has been provided. Per LUC Sec. 3.2.6.5.B.1, the building setback required from Tucson Blvd is based on the greater of, 21 feet or the building height measured from the back of future curb.

6. A note must be added to the site plan which states: "Vehicles may not back out into Tucson Blvd."

7. Dimension the setback from the proposed carport to the Drachman Street property line. Per LUC Sec. 3.2.6.5.A, the minimum building setback required from the front of the carport to the Drachman Street property line is based on the greater of 20 feet or 1 ½ times the carport height.

8. Provide a complete floor plan of the existing residence and the guest house to verify the number of bedrooms on-site. Bedroom. The term bedroom shall include all of the following.
A. Any room that is designated as a bedroom.
B. Any enclosed room which has a minimum area of sixty (60) square feet and has an accessible opening to the
exterior of the building in compliance with the International Building Code (IBC), whether termed a studio,
family room, study, den, bonus room, or any other name, except for a living room, dining room, kitchen, and
bathrooms.
C. Any room designated as a bedroom for the purpose of any other code requirement.

9. If this property contains two (2) single family dwellings, LUC Sec. 3.5.7.1.H states: For all lots containing two (2) or more single family dwellings, with the second dwelling having more than one bedroom, all parking and maneuvering must be located on-site, either in a side or rear perimeter yard. The vehicular use area must be improved, which includes surfacing, striping, and provisions of barriers in conformance with Development Standard 3-05.0. Vehicle parking spaces may not be located in a vehicular use area in any front street perimeter yard. Tandem parking or alley access is not allowed. (LUC Sec. 3.5.7.1.G)


If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608 ext. 1180. An appointment is required to discuss these comments in person.