Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04138
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/14/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
09/14/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
09/14/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
09/14/2004 | GERRY KOZIOL | WWM | REVIEW | Passed | |
09/14/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
09/14/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
09/14/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
09/14/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/14/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/14/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |