Permit Number: T04CM04111
Parcel: 137055220

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04111
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/04/2004 JIM EGAN FIRE REVIEW Approved
10/08/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/08/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
10/08/2004 ROBERT SHERRY WATER REVIEW Approved
10/08/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
10/08/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM04111 DENIED 10/04/04

1. Clarify which panel is to be used for new loads. Schedule is shown for Panel "TE". New lights and receptacles are shown on Electrical Plan as circuited from Panel "TI".
2. Show panel location on plans.
3. Indicate electrical loads on panel schedule for Circuits 16,17,18,24, and 26.
4. Indicate circuit number on Electrical Plan for Conf. Rm. receptacles.
10/08/2004 JIM TATE ENGINEERING REVIEW Approved
10/12/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/12/2004 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/12/2004 TAMI ACHONG OUT TO CUSTOMER Completed