Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04111
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/04/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/08/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/08/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/08/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/08/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 10/08/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM04111 DENIED 10/04/04 1. Clarify which panel is to be used for new loads. Schedule is shown for Panel "TE". New lights and receptacles are shown on Electrical Plan as circuited from Panel "TI". 2. Show panel location on plans. 3. Indicate electrical loads on panel schedule for Circuits 16,17,18,24, and 26. 4. Indicate circuit number on Electrical Plan for Conf. Rm. receptacles. |
| 10/08/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 10/12/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/12/2004 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/12/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |