Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T04CM04110
Parcel: 12417181C

Address:
1025 E 18TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T04CM04110
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/16/2004 Gerry Koziol WWM REVIEW Approved
10/11/2004 Neil Saunders BUILDING-RESIDENTIAL REVIEW Denied Plan Check Comments - Project #T04CM04110

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

General Requirements

1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned.
2. Pen and pencil corrections on final prints will not be acceptable. To avoid delays ensure all corrections have been made, are complete and have been coordinated on all-applicable details and notes.
3. Plans must comply with and reference the 2003 International Residential Code. Revise. (Electrical and Mechanical).

Floor Plan

1. Note and specify that shower enclosures shall have a minimum finished interior area of 1,024 square inches and shall be capable of encompassing a minimum 30" circle per 1994 UPC SEC. 410.0. All glass enclosures shall be tempered.
2. Show that each water closet is located in a clear space not less than 30" wide and has a clear space in front not less than 21" per figure R307.2.

Structural Plan

1. Joist schedule shows TJI's at 24"o/c and 16"o/c. Clarify.
2. Notes (pg. 5) - "Prefab wood "I" Joist" callout 18" TJI, 11-7/8" is called out elsewhere. Clarify.
3. Clarify and detail CC attachment to walls for Glulam Beam. 4/7 detail shows steel header. IRC provides no prescriptive method for this construction.
4. IRC provides no prescriptive method for braced wall design for 12' high wall. Justify braced wall design.

Electrical Plan

1. Callout water heater circuit on plan.
2. Where ceiling fans are shown on the plans, provide a note indicating only approved outlet boxes shall be used, per E4001.6.

If you have any questions, please contact your assigned plans examiner Neil Saunders at 791-5550, extension 1113.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/13/2004 TAMI ACHONG OUT TO CUSTOMER Completed
10/13/2004 ANGIE SHOFFSTALL REJECT SHELF Completed