Permit Number: T04CM04108
Parcel: 10321671B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04108
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
09/10/2004 ANY BUILDING-COMMERCIAL REVIEW Approved
09/10/2004 PATRICIA GEHLEN ZONING REVIEW Approv-Cond
09/13/2004 JIM EGAN FIRE REVIEW Approved
09/14/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/14/2004 ROBERT SHERRY WATER REVIEW Approved
09/14/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/15/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM04108 DENIED 9/14/04

Add a note near the panelboard referencing the series rating discussed as part of approved McGetrick plans (Wildan 10/14/04). Specify the series rating which the contractor shall maintain. Make it clear that the Contractor such specified series rating.

Eliminate any reference to "New" panels if such panels are existing.
09/15/2004 GERRY KOZIOL WWM REVIEW Approved