Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM04082
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/27/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/27/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
11/08/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide fixture descriptions for all plumbing fixtures (e.g. P-11). Reference Section 103.2.3, UPC 1994. 2. Sheets TA-4 and FA-1 note that the water heater is elevated. Coordinate with the other sheets. 3. Show the size and route of the T&P relief pipe from the water heater. Reference Section 608.5, UPC 1994. |