Permit Number: T04CM04082
Parcel: 130140260

Address:
4082 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM04082
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
10/27/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/08/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Provide fixture descriptions for all plumbing fixtures (e.g. P-11). Reference Section 103.2.3, UPC 1994.
2. Sheets TA-4 and FA-1 note that the water heater is elevated. Coordinate with the other sheets.
3. Show the size and route of the T&P relief pipe from the water heater. Reference Section 608.5, UPC 1994.