Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04CM04082
Parcel: 130140260

Address:
4082 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04082
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2004 Robert Suba ELECTRICAL-COMMERCIAL REVIEW Approved
09/17/2004 Jim Egan FIRE REVIEW Approved
09/21/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference Section 103.2.3, UPC 1994.
2. Show AC-3 and the gas piping to AC-3 on sheet P-1. Reference Section 103.2.3, UPC 1994.
3. Revise sheet P-3 so that details 1/P-3, 2/P-3, and 7/P-3 are completely shown on the sheet. Reference Section 103.2.3, UPC 1994.
4. Provide fixture descriptions for all plumbing fixtures (e.g. P-11 and the electric drinking fountain). Reference Section 103.2.3, UPC 1994.
5. Clarify the discrepancy in the piping shown in the water heater detail and detail 6/P-3. Reference Section 103.2.3, UPC 1994.
6. Sheet TA-1 notes that the water heater is elevated. Show how the water heater is to be supported and confirm that it complies with the access requirements of Section 511.0, UPC 1994 with AZ State amendments.
7. Show the size and route of the T&P relief pipe from the water heater. Reference Section 608.5, UPC 1994.
8. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping along with ½" insulation on the first eight feet of supply and discharge piping. Reference Sections 804.4 and 804.5, IECC 2000.
9. Provide combustion air openings for the water heater. Reference Section 507, UPC 1994 as amended by the State of Arizona.
10. Show the size, height, and termination of the water heater flue. Reference Section 103.2.3, UPC 1994.
11. Provide accessible cleanouts for the foot vents of the island fixtures (P-6 and FS) along with accessible upper terminal cleanouts for the fixture drains. Reference Sections 707.4 and 909.0, UPC 1994.
12. Provide upper terminal cleanouts for horizontal drain lines five feet or longer. Reference Section 707.4, UPC 1994.
13. Provide the missing sizes of the drain lines in detail 5/P-3. Reference Section 103.2.3, UPC 1994.
14. Provide the developed length of the water piping. Reference Section 103.2.3, UPC 1994.
15. Revise the water fixture units shown for the urinals per Section 610.10, UPC 1994. Revise the calculations to include any existing water fixtures that have not been included in the fixture unit tabulation (e.g. hose bibbs). Revise the pipe sizes as required.
16. Indicate if the hot water piping has been sized per Section 610.12 or 610.13, UPC 1994.
09/21/2004 ROBERT SHERRY WATER REVIEW Approved
09/21/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations by A/C unit to show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2000.
09/23/2004 Gerry Koziol WWM REVIEW Approved
09/30/2004 Raul Palma BUILDING-COMMERCIAL REVIEW Denied 1) A permit is required for awning at entry door.
2) Provide details of awning and the connection to the ext.
wall. Provide engineering calc`s for awning.
3) Sheet 3 of calc`s calls out a steel tube, where is this
tube on plans?
10/08/2004 David Rivera ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/12/2004 DELMA ROBEY OUT TO CUSTOMER Completed