Permit Number: T04CM04075
Parcel: 12317252B

Address:
1510 N VINE AV

Review Status: Completed

Review Details: REVISION

Permit Number - T04CM04075
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Provide backflow protection for the ice machine and the soda machine. If the indirect waste lines exceed 5 feet, provide a trap. Reference Sections 603.0 and 803.0, UPC 1994.
2. Provide the gas loads for the existing boiler and water heater. Reference Section 1216.2, UPC 1994.
3. If an approved grease interceptor is not installed in the existing building sewer, provide either a new grease interceptor or grease trap to protect the public sewer from grease. Reference Section 1011.1, UPC 1994.
10/19/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the duct-to-fan connections to comply with Sections 506.3.3.3 and 506.3.3.4, IMC 2000.
2. Provide a drain outlet at the bottom of the fan scroll and an approved grease reservoir for EF-1 per Section 506.3.8, IMC 2000.
3. Clarify how detail 102/M.1.2 is appropriate for EF-2.
4. Show how grease hood H-1 is to be supported from the existing structure. Reference Section 507.6, IMC 2000.
5. Confirm that the exhaust outlet of EF-1 is greater than 10 feet horizontally from the intake openings of EC-1. Reference Section 506.3.13.3, IMC 2000.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/22/2004 TAMI ACHONG OUT TO CUSTOMER Completed
10/22/2004 ANGIE SHOFFSTALL REJECT SHELF Completed