Permit Number: T04CM04074
Parcel: 12112062C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM04074
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the piping for the floor drain to use approved fittings. Reference Section 706.0, UPC 1994.
2. Revise the size of the air admittance valve for the floor sink and 3-compartment sink to correspont to the manufacturer's recommended size.
3. Provide access for the air admittance valves.
09/15/2004 TACHONG1 ENGINEERING REVIEW Needs Review
09/15/2004 TACHONG1 WWM REVIEW Needs Review
09/15/2004 TACHONG1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/15/2004 TAMI ACHONG OUT TO CUSTOMER Completed