Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM04042
Parcel: 119040200

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04042
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2004 JIM TATE ENGINEERING REVIEW Approved
09/07/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the water piping was sized. Reference Section 610.1, UPC 1994.
2. Show the size and location of the water meter and the reduced pressure backflow preventer on the drawing. Reference Section 103.2.3, UPC 1994.
09/07/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
09/07/2004 ROBERT SHERRY WATER REVIEW Approved
09/07/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide mechanical exhaust for the restroom. Reference Section 403.3, IMC 2000.
09/09/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
09/09/2004 GERRY KOZIOL WWM REVIEW Approved
09/14/2004 JIM EGAN FIRE REVIEW Approved
09/14/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/14/2004 BETH GRANT OUT TO CUSTOMER Completed