Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04041
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/07/2004 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 09/07/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the water piping was sized. Reference Section 610.1, UPC 1994. 2. Show the size and location of the water meter and the reduced pressure backflow preventer on the drawing. Reference Section 103.2.3, UPC 1994. |
| 09/07/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 09/07/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/07/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide mechanical exhaust for the restrooms. Reference Section 403.3, IMC 2000. |
| 09/09/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/09/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/14/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 09/14/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/14/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |