Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04027
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/21/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 09/21/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 09/21/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/21/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/21/2004 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 09/21/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/21/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 09/23/2004 | MELISSA POULIN | WWM | REVIEW | Approved | |
| 09/23/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM04027 DENIED 9/21/04 1. Ckt A-20, with 10 receptacles, appears low at 1800 VA. This is because of the Copier on one of the receptacles. 2. Panel A appears to be unbalanced. I get totals of 12,146 VA for Phase A and 8,912 VA for Phase B. This would result in over 100 A on Phase A. Please rebalance. 3. Please size new feeders to Panels B and C. 4. Please add existing Panel E to load calculations. Note that new Panel D has been double counted as part of Panel B load. 5. New Panel D is added to Panel B schedule. On line diagram this new panel is fed from Panel C. Please clarify. |