Permit Number: T04CM04027
Parcel: 121090090

Address:
5357 E PIMA ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04027
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2004 JIM EGAN FIRE REVIEW Approved
09/21/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/21/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
09/21/2004 ROBERT SHERRY WATER REVIEW Approved
09/21/2004 MICHAEL ST. PAUL ZONING REVIEW Approved
09/21/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/21/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
09/23/2004 MELISSA POULIN WWM REVIEW Approved
09/23/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM04027 DENIED 9/21/04


1. Ckt A-20, with 10 receptacles, appears low at 1800 VA. This is because of the Copier on one of the receptacles.
2. Panel A appears to be unbalanced. I get totals of 12,146 VA for Phase A and 8,912 VA for Phase B. This would result in over 100 A on Phase A. Please rebalance.
3. Please size new feeders to Panels B and C.
4. Please add existing Panel E to load calculations. Note that new Panel D has been double counted as part of Panel B load.
5. New Panel D is added to Panel B schedule. On line diagram this new panel is fed from Panel C. Please clarify.