Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM04009
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/02/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
09/02/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
09/02/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
09/03/2004 | CAGUILA1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
09/03/2004 | DAVE WITT | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
09/03/2004 | CAGUILA1 | WWM | REVIEW | Needs Review | |
09/03/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM04009 DENIED 9/2/04 1. Ckt 11 has Dining Room receptacles on Electrical Plan. Pls provide breaker size on panel schedule. 2. On Sheet E2 General Note A, and Smoke Detector Note A, change "1999 National Electrical Code" to "2002 National Electrical Code". Typical this project. 3. Provide conductor sizes for Ckts 1,3, Ckts 14,16, Ckts10,12, and for panel feeders. 4. Per NEC 210.12 (B) provide arc fault circuit interrupters on bedroom outlet branch circuits. 5. Provide for grounding per NEC Article 250. |
09/03/2004 | CAGUILA1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
09/03/2004 | DROBEY1 | WATER | REVIEW | Completed |