Permit Number: T04CM04009
Parcel: 13619194A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM04009
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2004 JIM EGAN FIRE REVIEW Approved
09/02/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
09/02/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
09/03/2004 CAGUILA1 PLUMBING-COMMERCIAL REVIEW Needs Review
09/03/2004 DAVE WITT BUILDING-COMMERCIAL REVIEW Needs Review
09/03/2004 CAGUILA1 WWM REVIEW Needs Review
09/03/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM04009 DENIED 9/2/04
1. Ckt 11 has Dining Room receptacles on Electrical Plan. Pls provide breaker size on panel schedule.
2. On Sheet E2 General Note A, and Smoke Detector Note A, change "1999 National Electrical Code" to "2002 National Electrical Code". Typical this project.
3. Provide conductor sizes for Ckts 1,3, Ckts 14,16, Ckts10,12, and for panel feeders.
4. Per NEC 210.12 (B) provide arc fault circuit interrupters on bedroom outlet branch circuits.
5. Provide for grounding per NEC Article 250.
09/03/2004 CAGUILA1 MECHANICAL-COMMERCIAL REVIEW Needs Review
09/03/2004 DROBEY1 WATER REVIEW Completed