Permit Number: T04CM03987
Parcel: 10321671B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03987
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Confirm that the specified water closet requires a minimum pressure of 15 PSIG.
09/01/2004 ROBERT SHERRY WATER REVIEW Approved
09/01/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/02/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
09/02/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
09/02/2004 DAN CASTRO ZONING REVIEW Approved
09/02/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM03987 DENIED 9/2/04
1. According to power plan, WH is on Panel E. There is no Panel E this project. Pls clarify and correct. WH not on Panel D this project.
2. Lights are on Panel C, according to Lighting Plans. Pls correct to Panel D.
09/10/2004 DROBEY1 WWM REVIEW Needs Review
09/10/2004 JIM EGAN FIRE REVIEW Approved