Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM03985
Parcel: 10321671B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03985
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Confirm that the specified water closet requires a minimum pressure of 15 PSIG.
09/01/2004 ROBERT SHERRY WATER REVIEW Approved
09/01/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/02/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
09/02/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
09/02/2004 DAN CASTRO ZONING REVIEW Approved
09/02/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
09/10/2004 DROBEY1 WWM REVIEW Needs Review
09/10/2004 JIM EGAN FIRE REVIEW Approved