Permit Number: T04CM03979
Parcel: 14043011A

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T04CM03979
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2004 Jim Egan FIRE REVIEW Approved
09/16/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/16/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the size, routing and termination of the condensate drain for the air conditioner. Condensate drains that terminate at or above grade outside the building must terminate in an area that is capable of absorbing the condensate flow without surface drainage. Reference Sections 307.2.1 and 307.2.2, IMC 2000 with local amendments.
09/16/2004 ROBERT SHERRY WATER REVIEW Passed
09/17/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please provide panel (feeder) load calculations and service load tabulation per NEC Article 220.
2. Reference Sheet E-7 and fixture cut sheets, it does not appear that fixture D meets the requirements of the Outdoor Lighting Code. Please provide full cutoff fixture, or drop wattage to 50W.
3. It is not clear from the cut sheet that Fixture D is suitable for a wet location. Please clarify.
4. There is a 5 KW unit heater on the Equipment Schedule Item 7 Sheet E-18. Not on plans or panel schedule. Please clarify intent.
10/01/2004 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied T04CM03976 .. 475 E ELVADO ROAD .. CONTROL BUILDING #2 ..
.. T04CM03977 .. 900 E SUSANA STREET .. CONTROL BUILDING #1..
.. T04CM03978 .. 900 E SUSANA STREET .. WALL AND ENCLOSURE ..
.. T04CM03979 .. 900 E SUSANA STREET .. CONTROL BUILDING #3 ..
.. DGL ..
.. BUILDING COMMENTS - 1st REVIEW


S1. Stepped foundations drawing CS-12, revise bottom of footings to comply with IBC Sec 1805.1, slope may not exceed 1:10 vs 1:2 on stepped footing details.
S2. Provide locations for buildings and structures by dimension from two adjacent property lines for each building or structure permitted.
S3. Provide structural calculations for footings and foundations , including stemwalls and address pipe and cable support design , attachment to and loads on masonry walls.
S4. Provide Inspection Program for Special Inspections required by Uniform Administrative Code Section #306, as amended .
S5. Special Inspection required for :
1. Masonry
2. Foundation excavation
3. Concrete
4. Field welding
5. Backfill
S6. Provide shop drawings for :
1. Precast concrete roof panels
2. Grating
S7. Detail connection of blocking to precast , ref details side bearing , edge flashing , end bearing option 1 and end bearing option 2, on drawing #CS-04.
S8. Field bending of reinforcing in masonry is not acceptable , please provide corner bars as dowels where required , ref side bearing and end bearing on drawing #CS-04.
S9. Provide complete structural calculations for buildings including lateral analysis and connection details.
S10. Provide toilet , ramps and level landings at mandoors , revise plans and show accessibile route per IBC and ANSI A117.1-1998 ed.
S11. Provide complete structural design including calculations and drawings for equipment platforms.
S12. Provide complete structural design including calculations and drawings for above ground tanks over 5000 gallons.
S13. Provide complete architectural and structural design including calculations and drawings for control building #2 and control building#3.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111
10/02/2004 DAN CASTRO ZONING REVIEW Passed
10/05/2004 LOREN MAKUS ENGINEERING REVIEW Passed
10/05/2004 Gerry Koziol WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/07/2004 LISA LESNY OUT TO CUSTOMER Completed
12/07/2004 ANGIE SHOFFSTALL REJECT SHELF Completed