Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T04CM03978
Parcel: 14043011A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM03978
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 1994 Uniform Plumbing Code with State of Arizona Amendments. WHILE THE LICENSED PLUMBERS WILL BE EXPECTED TO CONFORM TO THE REQUIREMENTS OF THE CURRENT CODE, IT IS ALSO EXPECTED THAT THE DESIGN OF THE PLUMBING SYSTEMS, AS SHOWN ON THE DRAWINGS, WILL CONFORM TO THE CURRENT CODES.
2. Show how the potable water piping for the treatment has been sized. Include all fixtures and the potable water requirements of the process equipment when calculating the total demand and determining pipe sizes. Reference Sections 610.1 and 610.5, UPC 1994. Note: Limit the water velocity to less than 8 fps for the CPVC piping and size the pipe per IAPMO IS 20-93. Reference Section A 6.1, UPC 1994; IAPMO IS 20-93, Section 610.0; and IAPMO IS 8-92, Section 610.1. NOTE: READ SECTIONS A1 THROUGH A5 (APPENDIX A, 1994 UPC), WHICH DESCRIBE HOW TO SIZE PLUMBING PIPING. THE MINIMUM RESIDUAL PRESSURE FOR A SAFETY EYEWASH/SHOWER IS 30 PSIG. THE FIXTURE UNIT VALUES SHOULD BE FROM TABLE A-2 (PUBLIC).
02/16/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approv-Cond

Final Status

Task End Date Reviewer's Name Type of Review Description
04/11/2005 KMEDINA1 OUT TO CUSTOMER Completed