Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/19/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The applicable code for all commercial plumbing projects is the 1994 Uniform Plumbing Code with State of Arizona Amendments. WHILE THE LICENSED PLUMBERS WILL BE EXPECTED TO CONFORM TO THE REQUIREMENTS OF THE CURRENT CODE, IT IS ALSO EXPECTED THAT THE DESIGN OF THE PLUMBING SYSTEMS, AS SHOWN ON THE DRAWINGS, WILL CONFORM TO THE CURRENT CODES. 2. Show how the potable water piping for the treatment has been sized. Include all fixtures and the potable water requirements of the process equipment when calculating the total demand and determining pipe sizes. Reference Sections 610.1 and 610.5, UPC 1994. Note: Limit the water velocity to less than 8 fps for the CPVC piping and size the pipe per IAPMO IS 20-93. Reference Section A 6.1, UPC 1994; IAPMO IS 20-93, Section 610.0; and IAPMO IS 8-92, Section 610.1. NOTE: READ SECTIONS A1 THROUGH A5 (APPENDIX A, 1994 UPC), WHICH DESCRIBE HOW TO SIZE PLUMBING PIPING. THE MINIMUM RESIDUAL PRESSURE FOR A SAFETY EYEWASH/SHOWER IS 30 PSIG. THE FIXTURE UNIT VALUES SHOULD BE FROM TABLE A-2 (PUBLIC). |
02/16/2005 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Approv-Cond |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/11/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |