Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM03978
Parcel: 14043011A

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T04CM03978
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2004 Jim Egan FIRE REVIEW Approved
09/15/2004 DAVID RIVERA ZONING REVIEW Passed
09/16/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
09/16/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 1994 Uniform Plumbing Code with State of Arizona Amendments.
2. Show how the potable water piping for the treatment has been sized. Include all fixtures and the potable water requirements of the process equipment when calculating the total demand and determining pipe sizes. Reference Sections 610.1 and 610.5, UPC 1994. Note: Limit the water velocity to less than 8 fps for the CPVC piping and size the pipe per IAPMO IS 20-93. Reference Section A 6.1, UPC 1994; IAPMO IS 20-93, Section 610.0; and IAPMO IS 8-92, Section 610.1.
3. Clarify the cross-connection control to be used for the three hose stations in the treatment facility and the external lube system for the SVE air blower. Potable water outlets with hose connections are required to comply with Section 603.3.6, UPC 1994 with AZ State amendments.
4. Provide freeze protection for 2"CPVC-3000, ¾"CPVC-3004, ¾"CPVC-3006, and ¾'CPVC-3000. Reference Section 313.6, UPC 1994.
09/16/2004 ROBERT SHERRY WATER REVIEW Approved
09/17/2004 Linda Buczynski ELECTRICAL-COMMERCIAL REVIEW Passed
10/01/2004 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied T04CM03976 .. 475 E ELVADO ROAD .. CONTROL BUILDING #2 ..
.. T04CM03977 .. 900 E SUSANA STREET .. CONTROL BUILDING #1..
.. T04CM03978 .. 900 E SUSANA STREET .. WALL AND ENCLOSURE ..
.. T04CM03979 .. 900 E SUSANA STREET .. CONTROL BUILDING #3 ..
.. DGL ..
.. BUILDING COMMENTS - 1st REVIEW


S1. Stepped foundations drawing CS-12, revise bottom of footings to comply with IBC Sec 1805.1, slope may not exceed 1:10 vs 1:2 on stepped footing details.
S2. Provide locations for buildings and structures by dimension from two adjacent property lines for each building or structure permitted.
S3. Provide structural calculations for footings and foundations , including stemwalls and address pipe and cable support design , attachment to and loads on masonry walls.
S4. Provide Inspection Program for Special Inspections required by Uniform Administrative Code Section #306, as amended .
S5. Special Inspection required for :
1. Masonry
2. Foundation excavation
3. Concrete
4. Field welding
5. Backfill
S6. Provide shop drawings for :
1. Precast concrete roof panels
2. Grating
S7. Detail connection of blocking to precast , ref details side bearing , edge flashing , end bearing option 1 and end bearing option 2, on drawing #CS-04.
S8. Field bending of reinforcing in masonry is not acceptable , please provide corner bars as dowels where required , ref side bearing and end bearing on drawing #CS-04.
S9. Provide complete structural calculations for buildings including lateral analysis and connection details.
S10. Provide toilet , ramps and level landings at mandoors , revise plans and show accessibile route per IBC and ANSI A117.1-1998 ed.
S11. Provide complete structural design including calculations and drawings for equipment platforms.
S12. Provide complete structural design including calculations and drawings for above ground tanks over 5000 gallons.
S13. Provide complete architectural and structural design including calculations and drawings for control building #2 and control building#3.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111
10/05/2004 Gerry Koziol WWM REVIEW Passed
10/05/2004 LOREN MAKUS ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/07/2004 LISA LESNY OUT TO CUSTOMER Completed
12/07/2004 ANGIE SHOFFSTALL REJECT SHELF Completed