Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/12/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a vent pipe for the floor drain located in the treatment building. Reference Section 901.1, UPC 1994. 2. Provide cleanouts in the building sewer at intervals not to exceed 100 feet. Reference Section 719.1, UPC 1994. 3. The detail of the water heater installation shows a ΒΌ" supply to the water heater. This does not comply with the recommendation of the manufacturer of the water heater. (Note: the specified water heater does not require an excess pressure relief valve. Reference Section 301.1.1, UPC 1994. |
04/14/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Plumbing plans call for Controlled Energy Corp. Water Heater RP3, which draws 20A. Approved plans provide a 20A circuit. Please coordinate with Plumbing and clarify. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/12/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |