Permit Number: T04CM03956
Parcel: 105102420

Address:
455 E WETMORE RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03956
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2004 JIM EGAN FIRE REVIEW Approved
08/31/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how water is to be connected to the relocated ice machine, including the required backflow protection.
2. Indicate where the ice machine is to be drained.
08/31/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM03956 DENIED 8/31/04
1. On Sheet A2 Oven is specified as 6000W, 240/208V. On Panel Schedule Oven is 1800W, 120V. Please coordinate and clarify.
2. Oven Warmer on Sheet A2 draws 12.3A. According to panel schedule at 0.75 KVA this equipment would draw only 6.25A. Please clarify.
3. Existing 60A Load Center is overloaded according to the panel load calculations submitted. Suggest the use of NEC Table 220.20 to determine compliance.
08/31/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify how the existing hood is to be modified.
08/31/2004 DAN CASTRO ZONING REVIEW Approved
08/31/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/01/2004 TACHONG1 WWM REVIEW Needs Review
10/01/2004 TACHONG1 BUILDING-COMMERCIAL REVIEW Needs Review
10/01/2004 TACHONG1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/01/2004 TAMI ACHONG OUT TO CUSTOMER Completed