Permit Number: T04CM03934
Parcel: 110055330

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03934
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM03934 DENIED 9/23/04

1. The minimum single-point wiring MCA for AC-1 and AC-2 is 52.4/55.5 for 208/230/1 service due to the electric heaters, per Bob Sherry, Mechanical Plans Examiner. Please specify panel load allocations, conductor sizes, and overcurrent protection accordingly.
2. As annotated and discussed in our telephone conversation, please maintain proper load counts on Ckts 35 and 36, and specification of #10 conductor size for Water Heater.
09/23/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/23/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/27/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
09/30/2004 EGRANT1 ENGINEERING REVIEW Needs Review
09/30/2004 EGRANT1 ZONING REVIEW Needs Review
09/30/2004 EGRANT1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/30/2004 BETH GRANT OUT TO CUSTOMER Completed