Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM03934
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/23/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM03934 DENIED 9/23/04 1. The minimum single-point wiring MCA for AC-1 and AC-2 is 52.4/55.5 for 208/230/1 service due to the electric heaters, per Bob Sherry, Mechanical Plans Examiner. Please specify panel load allocations, conductor sizes, and overcurrent protection accordingly. 2. As annotated and discussed in our telephone conversation, please maintain proper load counts on Ckts 35 and 36, and specification of #10 conductor size for Water Heater. |
| 09/23/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 09/23/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 09/27/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/30/2004 | EGRANT1 | ENGINEERING | REVIEW | Needs Review | |
| 09/30/2004 | EGRANT1 | ZONING | REVIEW | Needs Review | |
| 09/30/2004 | EGRANT1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/30/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |