Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T04CM03934
Parcel: 110055330

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03934
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved 1) PROVIDE CODE CHECK LIST.
2) ANSI STANDARDS 604.3.2 CLEARANCE FOR WATER CLOSET. CLARIFY.
3) CLARIFY SECURING OF 2HR WALL TO ROOF DECK.
08/30/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide access to the water heater, Reference Section 511.2, UPC 1994.
2. Revise the size of the water pipes per Section 610.4, UPC 1994.
3. Include all of the water fixtures in the fixture unit calculations (e.g. hoe bibb). Reference Section 610.1, UPC 1994.
4. The minimum pressure required for the specified water closet is greater than 15 psig.
5. Show that the faucet to be installed in the P-1 fixtures and the shower comply with the water conservation requirements and material standards of the 1994 UPC as modified by the State of Arizona.
6. Coordinate the DCW and DHW Isometric detail with the plumbing plan.
7. Provide a waste and vent riser diagram.
8. A 2" cleanout is not adequate for a 3" waste line. Reference Section 707.11, UPC 1994.
9. Provide an upper terminal cleanout for the waste piping in the bath room.. Reference Section 707.4, UPC 1994.
10. Show that the shower is handicapped accessible.
08/30/2004 ROBERT SHERRY WATER REVIEW Approved
08/30/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide statistical data to justify using the exception to Section 403.3 for the occcupant load.
2. Revise the ventilation calculations to show the outside air requirements by A/C unit and show how the outside air supplied by the units complies with Section 403.3.2, IMC 2000.
3. Coordinate the amount of outside air shown in the calculations with the outside air noted on the mechanical plan.
08/31/2004 JIM EGAN FIRE REVIEW Approved
09/01/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied
09/15/2004 LLESNY1 WWM REVIEW Needs Review
09/15/2004 LLESNY1 ZONING REVIEW Needs Review
09/15/2004 LLESNY1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/15/2004 LISA LESNY OUT TO CUSTOMER Completed