Permit Number - T04CM03926
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide calculations to show that the addition complies with the requirements of Section 101, International Energy Conservation Code, 2000.
2. Comment not addressed. Show that the modified sanctuary has sufficient ventilation. Reference Section 401, IMC 2000.
08/23/2005 PETER MCLAUGHLIN ZONING REVIEW Denied Site plan approval required.
08/26/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 8/30/05
ACTIVITY NUMBER: T04CM03926
PROJECT NAME: Westside Church of God
PROJECT ADDRESS: 1901 W. King Ave.
ARCHITECT / ENGINEER: Roger Lovstrom
PROJECT REVIEWER: CHRISTY FOREMAN



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Provide a north arrow on site plan
2) Provide documentation that exiting Parsonage has been permitted. It appears that work has been done without a permit on the Parsonage building. Foot print of building on site plan and provided documentation do not match. Is this a residence as stated in description ? Provided documentation makes this building appear to be a commercial building. Provide documentation that this was previously approved as a parsonage home.
3) Clarify means of egress illumination, section 1006. Clarify emergency power.
4) Clarify exit signs per section 1011. Exit sign for west door?
5) Detail 5/A-6 Clarify / Justify loading of existing CMU wall. Clarify connectors into existing masonry. Appears justification in structural calculations is still missing.
6) Provide clarification of restroom facilities meet requirements for table 2902.1. Per the IBC 2003 additional fixtures are required. A approved appeal to the building official will need to be provided to use fixture from adjacent building. Or further justification will need to be provided. Total site fixtures required and distance traveled to the facilities.
7) It appears restroom facilities do not meet the ANSI standards A117.1, section 1110.
08/31/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/31/2005 GBONILL1 OUT TO CUSTOMER Completed
08/31/2005 SUE REEVES REJECT SHELF Completed