Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T04CM03926
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/06/2005 | Jim Egan | FIRE | REVIEW | Approved | |
| 01/07/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 01/07/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations to show that the addition complies with the requirements of Section 101, International Energy Conservation Code, 2000. 2. Show that the modified sanctuary has sufficient ventilation. Reference Section 401, IMC 2000. |
| 01/07/2005 | Robert Sherry | WATER | REVIEW | Approved | |
| 01/20/2005 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. On Sheet A-1, please change the reference "2000 National Electrical Code" to "2002 National Electrical Code." 2. On Sheet A-7, please change the reference "2003 NEC" to "2002 NEC." 3. Provide IECC Lighting Power Budget calculations for new Activity Room. 4. Provide schedule and cut sheets for new lighting fixtures. Information shall clarify power requirements and shall be sufficient to allow evaluation for compliance with the Lighting Ordinance. 5. Provide circuit number for electrical load. 6. Provide panel schedule with totalizing load tabulations. |
| 01/20/2005 | PETER MCLAUGHLIN | ZONING | REVIEW | Denied | An approved site plan is required. |
| 01/26/2005 | Gerry Koziol | WWM | REVIEW | Approved | |
| 02/03/2005 | ELIZABETH EBERBACH | ENGINEERING | REVIEW | Approved | TO: Roger Gerard, applicant SUBJECT: Addition for Westside Church of God Engineering & Floodplain Review REVIEWER: Elizabeth Eberbach DATE: February 3, 2005 ACTIVITY NUMBER: T04CM03926 SUMMARY: Engineering has received and reviewed the Site Plan and Drainage Statement for site plan review, and recommends approval of the site plan. The Drainage Statement was accepted for review of this project only. The following conditions are applied to the project: SITE PLAN CONDITIONS: 1) Per Drainage Statement for the Westside Church of God (dated 1-3-5, DEI Job No.040902), water harvesting shall be provided within depressed landscaped feature areas; depressed areas shall be a minimum 6 inches deep. 2) There shall be no disturbance of wash area (FEMA SFHA FIRM Panel 2210K). 3) Provide temporary trash dumpster at site during construction. 4) Offsite disposal location for deleterious materials shall be placed in an approved and permitted site. No dumping in wash. 5) Temporary fencing will be installed around construction areas in order to prevent encroachment into the natural areas. 6) For any work performed within the right-of-way, contact the City of Tucson Department of Transportation Permits and Codes at (520) 791-4249. 7) Any revision to the Site Plan may require a re-submittal of the revised site plan for review. Contact DSD Engineering at 791-5550 to discuss changes in site plan design. For any questions, call me at 791-5550, extension 2204. Elizabeth Eberbach, PE Civil Engineer Engineering Division Development Services |
| 02/07/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 2/10/05 ACTIVITY NUMBER: T04CM03926 PROJECT NAME: Westside Church of God PROJECT ADDRESS: 1901 W. King Ave. ARCHITECT / ENGINEER: Roger Lovstrom PROJECT REVIEWER: CHRISTY FOREMAN TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1) Provide a north arrow on site plan 2) Provide documentation that exiting Parsonage has been permitted. 3) Table 602, 1 hour firewall required for east wall. 4) Clarify east wall complies with Table 704.8. 5) Clarify windows and doors comply with code section 715. 6) Clarify wall and ceiling finishes per section 803. 7) Clarify means of egress illumination, section 1006. Clarify emergency power. 8) Clarify hardware per section 1008.1.8 and 1008.1.8.3. 9) Clarify exit signs per section 1011. 10) Existing entry has 1 hr. fire-resistance rating per table 1016.1. See definition of corridor. 11) Clarify roof assembly is a Class 'C" roof assembly. 12) Provide a complete structural Analysis for addition. Justify footings and framing members. Meams, Headers, etc. Refer to Chapt. 16 of the 2003 IBC. 13) Soils report or footings must bear 18" below grade min. per City of Tucson Amendments section 1805.2. 14) Detail 5/A-6 Clarify / Justify loading of existing CMU wall. Clarify connectors into existing masonry. 15) Provide clarification of restroom facilities meet requirements for table 2902.1. 16) Clarify site meets chapt. 11 accessibility requirements section 1103, 1104, 1106, 1108, & 1109 with restroom facilities meeting ANSI standards A117.1, section 1110. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/14/2005 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 02/14/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |