Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
01/17/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide mechanical ventilation for the modified restrooms. Reference Section 403.3, IMC 2000.
01/17/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference Section 103.2.3, UPC 2000.
01/24/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Electrical plans Sheet A-7 have been eliminated from this project. If this is the intent, please remove references to the National Electrical Code and remove Electrical Plan from LIST OF DRAWINGS on the title sheet. Note that no electrical equipment will be executed on this permit, including that for any ventilation fans as required by the Mechanical Plans Examiner.