| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/24/2004 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 08/24/2004 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 08/26/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/27/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM03888 DENIED 8/26/04 1. Please clarify which gate operator is intended for this project. Note that ½ HP would draw 9.8 amps, and 1176 VA. One HP would draw 12.2 amps and 1464 VA. 2. Provide TEP available fault current. Demonstrate adequate rating of equipment. 3. Clarify how many poles are in this project (note indicates four poles, plan and panel schedule indicate only one). 4. Provide a disconnect for the gate motor, or justify otherwise. |