Permit Number: T04CM03888
Parcel: 13101055C

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE ONLY

Permit Number - T04CM03888
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
08/24/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
08/26/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
08/27/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM03888 DENIED 8/26/04
1. Please clarify which gate operator is intended for this project. Note that ½ HP would draw 9.8 amps, and 1176 VA. One HP would draw 12.2 amps and 1464 VA.
2. Provide TEP available fault current. Demonstrate adequate rating of equipment.
3. Clarify how many poles are in this project (note indicates four poles, plan and panel schedule indicate only one).
4. Provide a disconnect for the gate motor, or justify otherwise.