Permit Number: T04CM03869
Parcel: 110055550

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03869
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2004 JIM EGAN FIRE REVIEW Approved
08/26/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/26/2004 ROBERT SHERRY WATER REVIEW Approved
08/26/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/30/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM03869 DENIED 8/24/04
1. Please count the sign circuit at 1200VA per NEC 220.3 (B) (6), or justify otherwise.
2. Please consider the sign to be continuous load in load calculations.
3. It appears that the AC should have 1908 VA per phase, not 1236, and as largest motor 6651 VA not 4635. See Sheet M1, coordinate with Mechanical, and clarify.
08/30/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
08/31/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
09/03/2004 GERRY KOZIOL WWM REVIEW Approved
09/03/2004 DAN CASTRO ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/14/2004 DELMA ROBEY OUT TO CUSTOMER Completed