Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM03869
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/24/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/26/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/26/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/26/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/30/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04CM03869 DENIED 8/24/04 1. Please count the sign circuit at 1200VA per NEC 220.3 (B) (6), or justify otherwise. 2. Please consider the sign to be continuous load in load calculations. 3. It appears that the AC should have 1908 VA per phase, not 1236, and as largest motor 6651 VA not 4635. See Sheet M1, coordinate with Mechanical, and clarify. |
| 08/30/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 08/31/2004 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/03/2004 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/03/2004 | DAN CASTRO | ZONING | REVIEW | Approved |