Permit Number: T04CM03867
Parcel: 10712189B

Address:
308 W GLENN ST

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE ONLY

Permit Number - T04CM03867
Review Name: COMMERCIAL-BLDG/FIRE ONLY
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify how the ventilation rates have been selected for the project.
08/30/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show where the 163 CFH for the exisrting A/C unit branches off from the piping shown on the drawing.
09/01/2004 TACHONG1 BUILDING-COMMERCIAL REVIEW Needs Review
09/01/2004 TACHONG1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/01/2004 TAMI ACHONG OUT TO CUSTOMER Completed