Permit Number: T04CM03866
Parcel: 105102430

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03866
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2004 JIM EGAN FIRE REVIEW Approved
08/26/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/26/2004 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
08/26/2004 ROBERT SHERRY WATER REVIEW Approved
08/26/2004 PETER MCLAUGHLIN ZONING REVIEW Approved
08/26/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/26/2004 BLANCA ESPINO ENGINEERING REVIEW Approved
08/30/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM03866 DENIED 8/26/04
1. It appears that #8 conductor, or ampacity 50 amps, since the load on the AC would be 53.7A at continuous load.
2. For the new service lateral, the #6 GND on the line side of the disconnect would consist of a redundant path to ground. Please remove.
3. Please diagram the new and existing service-related equipment in sufficient detail to evaluate the requirements of NEC 230.2, Number of Services. Show exact location of existing equipment in plan view. Show the spacial relationship of new and existing equipment on an equipment diagram.
09/07/2004 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/07/2004 LISA LESNY OUT TO CUSTOMER Completed