Permit Number: T04CM03846
Parcel: 125130440

Address:
3202 E 1ST ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T04CM03846
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/20/2004 PATRICIA GILBERT ENGINEERING REVIEW Approved
08/23/2004 MELISSA POULIN WWM REVIEW Approved
08/23/2004 DAN CASTRO ZONING REVIEW Approved
08/23/2004 JIM EGAN FIRE REVIEW Approved
08/30/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the piping has been sized. Reference Section 610.4, UPC 1994.
08/30/2004 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
08/30/2004 ROBERT SHERRY WATER REVIEW Approved
08/30/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T04CM03846 DENIED 8/30/04
1. Provide circuit for Electric Water Cooler. Coordinate with Sheet2 P1.1 and P1.2.
2. Size feeder to new Panel A.
3. Please correct Phase B load tabulation to 381 A.
4. Indicate size of existing service.
5. Indicate service equipment on plans.
08/30/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The tailpiece of a breakroom sink is not an appropriate termination for the condensate drain of the heat pump.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/30/2004 TAMI ACHONG OUT TO CUSTOMER Completed