Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T04CM03846
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/20/2004 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 08/23/2004 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 08/23/2004 | MELISSA POULIN | WWM | REVIEW | Approved | |
| 08/23/2004 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/30/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the piping has been sized. Reference Section 610.4, UPC 1994. |
| 08/30/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The tailpiece of a breakroom sink is not an appropriate termination for the condensate drain of the heat pump. |
| 08/30/2004 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/30/2004 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/30/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04CM03846 DENIED 8/30/04 1. Provide circuit for Electric Water Cooler. Coordinate with Sheet2 P1.1 and P1.2. 2. Size feeder to new Panel A. 3. Please correct Phase B load tabulation to 381 A. 4. Indicate size of existing service. 5. Indicate service equipment on plans. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/30/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |