Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM03823
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2005 | Christy Foreman | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 1/03/05 ACTIVITY NUMBER: T04CM03823 PROJECT NAME: ACTIVITY BLDG. RICHEY ELEMENTARY SCHOOL PROJECT ADDRESS: 2209 N. 15TH AVE ARCHITECT / ENGINEER: CDG ARCHITECTS PROJECT REVIEWER: CHRISTY FOREMAN TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1. OCCUPANT LOAD = 355 THEREFORE 178 MALE AND 178 FEMALE. 178/125 = 1.4 W.C MALE THEREFORE = 2 WATER CLOSETS OR 1 W.C. & 1 URINAL 178/65 = 2.7 W.C. FEMALE THEREFORE = 3 WATER CLOSETS TOTAL FIXTURES (MALE, FEMALE, & UNISEX) = 30 + 2 (NEW) = 32 TOTAL FIXURES REQUIRED = 30(EXISTING) + 5 (NEW) = 35 (TOTAL FIXTURES REQUIRED) THEREFORE FIXTURE COUNT IS STILL SHORT 3 FIXTURES. I SPOKE WITH DAVE MANN AND HE WAS WILLING TO ACCOMMODATE LESS FIXTURES FOR THE NEW BUILDING IF THE TOTAL FIXTURE COUNT ON CAMPUS MADE UP FOR THE ONES LACKING. THEREFORE ADDITIONAL FIXTURES STILL NEED TO BE PROVIDED. |
| 12/09/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/09/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/04/2005 | BETH GRANT | OUT TO CUSTOMER | Completed |
| 01/04/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |