Permit Number: T04CM03823
Parcel: 11515284A

Address:
2209 N 15TH AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM03823
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/24/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not addressed. Revise the energy code calculations to match the proposed building. Provide sufficient information on the plans (e.g. call out the R-value for the roof insulation) and specifications to demonstrate conformance to the energy conservation code. Reference Section 104.2, IECC 2000.
11/24/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied Revise the sizes of the water pipes to correspond to the provided calculations. Reference Appendix A, UPC 1994.
11/26/2004 Christy Foreman BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 11/26/04
ACTIVITY NUMBER: T04CM03823
PROJECT NAME: ACTIVITY BLDG. RICHEY ELEMENTARY SCHOOL
PROJECT ADDRESS: 2209 N. 15TH AVE
ARCHITECT / ENGINEER: CDG ARCHITECTS
PROJECT REVIEWER: CHRISTY FOREMAN

TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1. OCCUPANT LOAD = 355 THEREFORE 178 MALE AND 178 FEMALE.
178/125 = 1.4 W.C MALE THEREFORE = 2 WATER CLOSETS OR 1 W.C. & 1 URINAL
178/65 = 2.7 W.C. FEMALE THEREFORE = 3 WATER CLOSETS
TOTAL FIXTURES (MALE, FEMALE, & UNISEX) = 30 + 2 (NEW) = 32
TOTAL FIXURES REQUIRED = 30(EXISTING) + 5 (NEW) = 35 (TOTAL FIXTURES REQUIRED)

THEREFORE FIXTURE COUNT IS STILL SHORT 3 FIXTURES.

I SPOKE WITH DAVE MANN AND HE WAS WILLING TO ACCOMMODATE LESS FIXTURES FOR THE NEW BUILDING IF THE TOTAL FIXTURE COUNT ON CAMPUS MADE UP FOR THE ONES LACKING. THEREFORE ADDITIONAL FIXTURES STILL NEED TO BE PROVIDED.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/29/2004 TAMI ACHONG OUT TO CUSTOMER Completed
11/29/2004 ANGIE SHOFFSTALL REJECT SHELF Completed