Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM03823
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/06/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Revise the energy code calculations to match the proposed building. Provide sufficient information in the plans and specifications to demonstrate conformance to the energy conservation code. Reference Section 104.2, IECC 2000. 2. The provided sequence of operation for the CO2 sensors (sheet 15.1) indicates that the maximum amount of outside air to be provided by the HVAC system when the facility is fully occupied is only 50% of the required amount of outside air. Revise the controls to provide the required amount of outside air to the space. Reference Section 405.1, IMC 2000. 3. Clarify the design of the exhaust system with respect to the number of inlets. Reference Section 106.3.1, IMC 2000. |
| 10/06/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed on the architectural plans. Provide the sizes of the scuppers shown on the plans. Provide overflow protection for the roof. Reference Appendix D, UPC 1994. 2. Comment not addressed. Show the size and route of the water line serving the proposed building along with the size and location of the water meter and RPBP. Reference Section 610.0, UPC 1994. 3. Use the minimum available water pressure as the design pressure for the water calculations. Verify that the developed length of the existing water supply is only 500 feet. Revise the sizes of the branch water pipes as required. Reference Appendix A 1.1, UPC 1994. |
| 10/12/2004 | Christy Foreman | BUILDING-COMMERCIAL | REVIEW | Denied | 1) SHT 16.1 EXIT LIGHT OVER WINDOW INSTEAD OF DOOR. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/14/2004 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 10/14/2004 | SUE REEVES | REJECT SHELF | Completed |